+86-0431-84158222
+86-0431-84155885
|
S/N |
Item |
Unit |
Parameters |
|
1 |
Rated voltage |
kV |
12 |
|
2 |
Rated frequency |
Hz |
50/60 |
|
3 |
Rated current |
A |
630 |
|
4 |
Rated short-time withstand current |
kA |
20 |
|
5 |
Rated peak withstand current |
kA |
50 |
|
6 |
Rated duration of short-circuit |
s |
4 |
|
7 |
Rated short-circuit open current |
kA |
20 |
|
8 |
Rated short-circuit closing current (peak) |
kA |
50 |
|
9 |
Rated operation sequence |
O-0.3s-CO-180s-CO |
|
|
10 |
Rated active load breaking current |
A |
630 |
|
11 |
Power frequency voltage (1min) (phase-to-ground, phase-to-phase and phase-to-fracture) |
kV |
42/48 |
|
12 |
Lightening impulse withstand voltage (phase-to-ground, phase-to-phase and phase-to-fracture) |
kV |
75/85 |
|
13 |
Rated cable-charging breaking current |
A |
10 |
|
14 |
Mechanical life |
Time |
10000 |
|
15 |
Clearance between open contacts |
mm |
8±1 |
|
16 |
Over-travel of the contact |
mm |
2.5~4 |
|
17 |
Contact closing bounce time |
ms |
≤10 |
|
18 |
Three-phase closing/opening non-synchronism |
ms |
≤3 |
|
19 |
Sulfur hexafluoride gas rated pressure |
MPa |
“0” |
|
20 |
Enclosure protection class |
IP67 |